Standard and Approval
<HAR> HD 22.9 S2, VDE-0282 Part-9, BS 7211, IEC 60754-2, EN 50267, VDE 0482-267, CE Low Voltage
Directive 73/23/EEC and 93/68/EEC, ROHS compliant
Cable Construction
Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5 BS 6360 cl. 5, HD 383
Cross-link polyolefin EI5 core insulation
LSOH - low smoke, zero halogen
Technical Characteristics
Working voltage: 300/500v (H05Z-K), 450/750v (H07Z-K)
Test voltage: 2500 volts
Flexing bending radius: 8 x Ø
Static bending radius: 8 x Ø
Flexing temperature: -15º C to +90º C
Static temperature: -40º C to +90º C
Flame retardant: IEC 60332.1
Insulation resistance: 10 MΩ x km
Smoke density acc. to EN 50268 / IEC 61034
Corrosiveness of combustion gases acc. to EN 50267-2-2, IEC 60754-2
Flame test: flame-retardant acc. to EN 50265-2-1, IEC 60332.1
Cable Parameter
AWG
|
No. of Cores x Nominal Cross Sectional Area # xmm²
|
Nominal Thickness of Insulation mm
|
Nominal Overall Diameter mm
|
Nominal Copper Weight kg/Km
|
Nominal Weight kg/Km
|
20(16/32)
|
1 x 0.5
|
0.6
|
2.3
|
4.8
|
9
|
18(24/32)
|
1 x 0.75
|
0.6
|
2.5
|
7.2
|
12.4
|
17(32/32)
|
1 x 1
|
0.6
|
2.6
|
9.6
|
15
|
H07Z-K
|
|||||
16(30/30)
|
1 x 1.5
|
0.7
|
3.5
|
14.4
|
24
|
14(50/30)
|
1 x 2.5
|
0.8
|
4
|
24
|
35
|
12(56/28)
|
1 x 4
|
0.8
|
4.8
|
38
|
51
|
10(84/28)
|
1 x 6
|
0.8
|
6
|
58
|
71
|
8(80/26)
|
1 x 10
|
1.0
|
6.7
|
96
|
118
|
6(128/26)
|
1 x 16
|
1.0
|
8.2
|
154
|
180
|
4(200/26)
|
1 x 25
|
1.2
|
10.2
|
240
|
278
|
2(280/26)
|
1 x 35
|
1.2
|
11.5
|
336
|
375
|
1(400/26)
|
1 x 50
|
1.4
|
13.6
|
480
|
560
|
2/0(356/24)
|
1 x 70
|
1.4
|
16
|
672
|
780
|
3/0(485/24)
|
1 x 95
|
1.6
|
18.4
|
912
|
952
|
4/0(614/24)
|
1 x 120
|
1.6
|
20.3
|
1152
|
1200
|
1 x 150
|
1.8
|
22.7
|
1440
|
1505
|
|
350 MCM (944/24)
|
1 x 185
|
2.0
|
25.3
|
1776
|
1845
|
500MCM(1225/24)
|
1 x 240
|
2.2
|
28.3
|
2304
|
2400
|